15.2.23 [035] Smart Meter Verification Aborted
Alert
Function Check Failed or Smart Meter Verification Aborted
Cause
The SMV test did not complete, possibly because it was manually aborted or because process conditions were
too unstable.
Recommended actions
1. Minimize process instability and repeat the test.
2. Check the SMV abort code and take appropriate steps.
3. Contact customer service.
15.2.24 [100] mA Output 1 Saturated
Alert
Output Saturated
Cause
The calculated output value is outside the range of the output.
Recommended actions
1. Check the settings of
Upper Range Value
and
Lower Range Value
.
Configure Lower Range Value (LRV) and Upper Range Value (URV) for the mA Output
2. Check your process conditions against the values reported by the device.
3. Ensure that both devices are using the same measurement unit.
4. Purge the sensor tubes.
15.2.25 [101] mA Output 1 Fixed
Alert
Output Fixed
Cause
One of the following conditions have occurred:
•
The HART address is set to a non-zero value
•
A loop test is running
•
The output is configured to send a constant value (
mA Output Action
or
Loop Current Mode
)
Recommended actions
1. Check the HART address and
mA Output Action
, or
Loop Current Mode
.
2. Check to see if a loop test is in process (the output is fixed).
Troubleshooting
Configuration and Use Manual
April 2019
MMI-20048166
166
Micro Motion 4200 Transmitters