Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
12
Affinity User Guide
www.controltechniques.com Issue Number: 5
For size 1 to 6 standard drives, size 1 to 3 E12/54 drives, and size 1 to 3 E12/E66 drives, the continuous current ratings given are for maximum 40
°
C
(104
°
F),1000m altitude and 3.0kHz switching. For size 4 to 6 E12/54 drives, the continuous current ratings given are for maximum 35
°
C
(95
°
F),1000m altitude and 3.0kHz switching. For further information refer to section 12.1.1
Power and current ratings (Derating for switching
Table 2-2 400V Drive ratings (380V to 480V ±10%)
Model
Maximum continuous
output current
Nominal power
at 400V
Motor power
at 460V
Peak current
A
kW
hp
A
1401
2.8
1.1
1.5
3.0
1402
3.8
1.5
2.0
4.1
1403
5.0
2.2
3.0
5.5
1404
6.9
3.0
5.0
7.5
1405
8.8
4.0
5.0
9.6
1406
11
5.5
7.5
12.1
2401
15.3
7.5
10
16.8
2402
21
11
15
23
2403
29
15
20
31
3401
35
18.5
25
38
3402
43
22
30
47
3403
56
30
40
61
4401
68
37
50
74
4402
83
45
60
91
4403
104
55
75
114
5401
138
75
100
151
5402
168
90
125
184
6401
205
110
150
225
6402
236
132
200
259
1
2
3
4
55
56
Summary of Contents for Affinity