Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
192
Affinity User Guide
www.controltechniques.com Issue Number: 5
Parameter
Range(
Ú
)
Default(
Ö
)
Type
OL
RFC
OL
RFC
14.01
PID 1 control output
±100.00 %
RO
Bi
NC PT
14.02
PID 1 main reference source
Pr
1.00
to Pr
50.99
Pr
0.00
RW Uni
PT US
14.03
PID 1 reference source
RW Uni
PT US
14.04
PID 1 feedback source
RW Uni
PT US
14.05
PID 1 reference invert
OFF (0) or On (1)
OFF (0)
RW Bit
US
14.06
PID 1 feedback invert
RW Bit
US
14.07
PID 1 reference slew-rate limit
0.0 to 3,200.0 s
0.0
RW Uni
US
14.08
PID 1 enable
OFF (0) or On (1)
OFF (0)
RW Bit
US
14.09
PID 1 optional enable source
Pr
1.00
to Pr
50.99
Pr
10.01
RW Uni
PT US
14.10
PID 1 proportional gain
0.000 to 4.000
1.000
RW Uni
US
14.11
PID 1 integral gain
0.500
RW Uni
US
14.12
PID 1 derivative gain
0.000
RW Uni
US
14.13
PID
1 output upper limit
0.00 to 100.00 %
100.00
RW Uni
US
14.14
PID
1 output lower limit
±100.00 %
-100.00
RW
Bi
US
14.15
PID 1 output scaling
0.000 to 4.000
1.000
RW Uni
US
14.16
PID 1 output destination
Pr
1.00
to Pr
50.99
Pr
0.00
RW Uni DE
PT US
14.17
PID 1 hold integrator enable
OFF (0) or On (1)
OFF (0)
RW Bit
NC
US
14.18
PID 1 symmetrical limit enable
RW Bit
US
14.19
PID 1 main reference
±100.00 %
RO
Bi
NC PT
14.20
PID 1 reference
RO
Bi
NC PT
14.21
PID 1 feedback
RO
Bi
NC PT
14.22
PID 1 error
RO
Bi
NC PT
14.23
PID 1 reference scaling
0.000 to 4.000
1.000
RW Uni
US
14.24
PID 1 feedback scaling
RW Uni
US
14.25
PID 1 digital reference
±100.00 %
0.00
RW
Bi
NC
14.26
PID 1 digital feedback
RW
Bi
NC
14.27
PID 1 optional enable source parameter 2
0.00 to 50.99
RW Uni
PT US
14.28
PID 1 pre-sleep boost level
0.00 to 100.00 %
RW Uni
US
14.29
Maximum boost time
0.0 to 250.0 s
0.0
RW Uni
US
14.30
PID 1 pre-sleep boost level enable
OFF (0) or On (1)
RO
Bit
NC PT US
14.31
PID 2 output
±100.00 %
RO
Bi
NC PT
14.33
PID 2 reference source
Pr
0.00
to
50.99
Pr
0.00
RW Uni
PT US
14.34
PID 2 feedback source
RW Uni
PT US
14.35
PID 2 reference invert
OFF (0) or On (1)
OFF (0)
RW Bit
US
14.36
PID 2 feedback invert
RW Bit
US
14.37
PID 2 reference slew-rate limit
0.0 to 3,200.0 s
0.0
RW Uni
US
14.38
PID 2 enable
0 to 2
0
RW Uni
US
14.40
PID 2 proportional gain
0.000 to 4.000
1.000
RW Uni
US
14.41
PID 2 integral gain
0.500
RW Uni
US
14.42
PID 2 derivative gain
0.000
RW Uni
US
14.43
PID 2 output upper limit
0.00 to 100.00 %
100.00
RW Uni
US
14.44
PID 2 output lower limit
±100.00 %
-100.00
RW
Bi
US
14.45
PID 2 output scaling
0.000 to 4.000
1.000
RW Uni
US
14.46
PID 2 output destination
Pr
1.00
to Pr
50.99
Pr
0.00
RW Uni DE
PT US
14.47
PID 2 hold integrator enable
OFF (0) or On (1)
OFF (0)
RW Bit
NC
US
14.48
PID 2 symmetrical limit enable
RW Bit
US
14.50
PID 2 reference
±100.00 %
RO
Bi
NC PT
14.51
PID 2 feedback
RO
Bi
NC PT
14.52
PID 2 error
RO
Bi
NC PT
14.53
PID 2 reference scaling
0.000 to 4.000
1.000
RW Uni
US
14.54
PID 2 feedback scaling
RW Uni
US
14.55
PID 2 digital reference
±100.00 %
0.00
RW
Bi
NC
14.56
PID 2 digital feedback
RW
Bi
NC
14.58
PID 1 Feedback output scaling
0.00 to 4.000
1.000
RW Uni
US
14.59
PID mode selector
0 to 7
0
RW Uni
US
14.60
PID 1 Square root enable
OFF (0) or On (1)
OFF (0)
RW Bit
US
14.61
PID 2 Square root enable
RW Bit
US
14.62
Combined square root enable
RW Bit
US
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not copied
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save
Summary of Contents for Affinity