Parameter
Range(
Ú
)
Default(
Ö
)
Type
OL
RFC
OL
RFC
12.01
Threshold detector 1 output
OFF (0) or On (1)
RO
Bit
NC PT
12.02
Threshold detector 2 output
OFF (0) or On (1)
RO
Bit
NC PT
12.03
Threshold detector 1 source
Pr
1.00
to Pr
50.99
Pr
0.00
RW Uni
PT US
12.04
Threshold detector 1 level
0.00 to 100.00 %
0.00
RW Uni
US
12.05
Threshold detector 1 hysteresis
0.00 to 25.00 %
0.00
RW Uni
US
12.06
Threshold detector 1 output
invert
OFF (0) or On (1)
OFF (0)
RW Bit
US
12.07
Threshold detector 1 destination
Pr
1.00
to Pr
50.99
Pr
0.00
RW Uni DE
PT US
12.08
Variable selector 1 source 1
RW Uni
PT US
12.09
Variable selector 1 source 2
RW Uni
PT US
12.10
Variable selector 1 mode
Select input 1 (0), select input 2 (1), add (2),
subtract (3), multiply (4), divide (5),
time constant (6), linear ramp (7), modulus (8),
powers (9), sectional control (10),
external rectifier monitor (11)
Select input 1 (0)
RW Uni
US
12.11
Variable selector 1 destination
Pr
1.00
to Pr
50.99
Pr
0.00
RW Uni DE
PT US
12.12
Variable selector 1 output
±100.00 %
RO
Bi
NC PT
12.13
Variable selector 1 source 1
scaling
±4.000
1.000
RW
Bi
US
12.14
Variable selector 1 source 2
scaling
RW
Bi
US
12.15
Variable selector 1 control
0.00 to 100.00 s
0.00
RW Uni
US
12.23
Threshold detector 2 source
Pr
1.00
to Pr
50.99
Pr
0.00
RW Uni
PT US
12.24
Threshold detector 2 level
0.00 to 100.00 %
0.00
RW Uni
US
12.25
Threshold detector 2 hysteresis
0.00 to 25.00 %
RW Uni
US
12.26
Threshold detector 2 output
invert
OFF (0) or On (1)
OFF (0)
RW Bit
US
12.27
Threshold detector 2 destination
Pr
1.00
to Pr
50.99
Pr
0.00
RW Uni DE
PT US
12.28
Variable selector 2 source 1
RW Uni
PT US
12.29
Variable selector 2 source 2
RW Uni
PT US
12.30
Variable selector 2 mode
Select input 1 (0), select input 2 (1), add (2),
subtract (3), multiply (4), divide (5),
time constant (6), linear ramp (7), modulus (8),
powers (9), sectional control (10),
external rectifier monitor (11)
Select input 1 (0)
RW Uni
US
12.31
Variable selector 2 destination
Pr
1.00
to Pr
50.99
Pr
0.00
RW Uni DE
PT US
12.32
Variable selector 2 output
±100.00 %
RO
Bi
NC PT
12.33
Variable selector 2 source 1
scaling
±4.000
1.000
RW
Bi
US
12.34
Variable selector 2 source 2
scaling
RW
Bi
US
12.35
Variable selector 2 control
0.00 to 100.00 s
0.00
RW Uni
US
12.40
Brake release indicator
OFF (0) or On (1)
RO
Bit
NC PT
12.41
Brake controller enable
dis (0), rEL (1 ), d IO (2), USEr (3)
dis (0)
RW Txt
US
12.42
Upper current threshold
0 to 200 %
50
RW Uni
US
12.43
Lower current threshold
0 to 200 %
10
RW Uni
US
12.44
Brake release frequency
0.0 to 20.0 Hz
1.0
RW Uni
US
12.45
Brake apply frequency / speed
0 to 200 rpm
2.0
5
RW Bit
US
12.46
OL> Pre-brake release delay
0.0 to 25.0 s
1.0
RW Uni
US
RFC> Brake apply speed delay
1.0
12.47
Post brake release delay
1.0
RW Uni
US
12.48
Brake apply delay
0.0 to 25.0 s
1.0
RW Uni
US
The brake control functions are provided to allow well co-ordinated operation of an external brake with the drive. While both hardware
and software are designed to high standards of quality and robustness, they are not intended for use as safety functions, i.e. where a
fault or failure would result in a risk of injury. In any application where the incorrect operation of the brake release mechanism could result
in injury, independent protection devices of proven integrity must also be incorporated.
WARNING
Summary of Contents for Affinity