11.21 Advanced features
This section gives information on some of the advanced functions of the
drive. For additional information see the
Advanced User Guide
.
11.21.1 Reference modes
If Pr
8.39
is set to OFF (0), then the setting of Pr
1.14
automatically
changes the operation of digital inputs T28 and T29 by configuring the
destination parameters Pr
8.25
and Pr
8.26
. To allow Pr
8.25
and Pr
8.26
to be changed manually by the user, the automatic set-up must be
disabled by setting Pr
8.39
to 1.
If Pr
8.39
is 0 and Pr
1.14
is changed, then a drive reset is required
before the function of terminal T28 or T29 will become active.
* Setting Pr
1.15
to 9 enables the Preset reference scan timer. With the scan timer enabled analog 1 and preset references 2 to 8 are selected
automatically in turn. Pr
1.16
defines the time between each change.
Reference modes
Pr
1.14
, Pr
1.15
and Pr
8.39
Hand / off / auto
Pr
1.52
Fire mode
Pr
1.53
and Pr
1.54
Advanced process PID
Menu 14
Analog reference profile
Pr
7.41
and Pr
7.44
Braking modes
Pr
2.04
and Pr
2.08
S ramps
Pr
2.06
and Pr
2.07
Torque modes
Pr
4.08
and Pr
4.11
Stop modes
Pr
6.01
, Pr
6.06
, Pr
6.07
and Pr
6.08
Main loss modes
Pr
6.03
, Pr
6.48
, Pr
4.13
and Pr
4.14
Catch a spinning motor
Pr
6.09
and Pr
5.40
Fast disable
Pr
6.29
Building automation interface Menu 17
1.14
Reference selector
RW
Txt
NC
US
Ú
A1.A2 (0), A1.Pr (2), A2.Pr (2),
Pr (3), PAd (4), Prc (5)
Ö
A1.A2 (0)
1.15
Preset reference selector
RW
Uni
NC
US
Ú
0 to 9
Ö
0
8.39
T28 and T29 auto-selection disable
RW
Bit
US
Ú
OFF (0) or On (1)
Ö
On (1)
Table 11-8 Active reference
Pr 1.14
Pr 1.15
Digital Input T28
Digital Input T29
Pr 1.49
Pr 1.50
Active Reference
State
Function
State
Function
A1.A2
(0)
0 or 1
0
Analog 1/2 select
No function
1
1
Analog input 1
1
2
1
Analog input 2
2 to 8
No function
1 or 2
2 to 8
Preset reference 2 to 8
9 *
0
Analog 1/2 select
1
1
Analog input 1
1
2
1
Analog input 2
No function
1 or 2
2 to 8
Preset reference 2 to 8
A1.Pr
(1)
0
0
Preset select bit 0
0
Preset select bit 1
1
1
Analog input 1
1
2
Preset reference 2
0
1
3
Preset reference 3
1
4
Preset reference 4
1
No function
No function
1
Analog input 1
2 to 8
2 to 8
Preset reference 2 to 8
9 *
1
Analog input 1
2 to 8
Preset reference 2 to 8
A2.Pr
(2)
0
0
Preset select bit 0
0
Preset select bit 1
2
1
Analog input 2
1
2
Preset reference 2
0
1
3
Preset reference 3
1
4
Preset reference 4
1
No function
No function
1
Analog input 2
2 to 8
2 to 8
Preset reference 2 to 8
9 *
1
Analog input 2
2 to 8
Preset reference 2 to 8
Pr
(3)
0
0
Preset select bit 0
0
Preset select bit 1
3
1
Preset reference 1
1
2
Preset reference 2
0
1
3
Preset reference 3
1
4
Preset reference 4
1 to 8
No function
No function
1 to 8
Preset reference 1 to 8
9 *
1 to 8
Preset reference 1 to 8
PAd
(4)
No function
No function
4
Keypad reference
Prc
(5)
No function
No function
5
Precision reference