Cable sizes are from IEC60364-5-52:2001 table A.52.C with correction
factor for 40°C ambient of 0.87 (from table A52.14) for cable installation
method B2 (multicore cable in conduit).
Only PVC insulated cables should be used.
Cable size may be reduced if a different installation method is used, or if
the ambient temperature is lower.
The recommended cable sizes above are only a guide. The mounting
and grouping of cables affects their current-carrying capacity, in some
cases smaller cables may be acceptable but in other cases a larger
cable is required to avoid excessive temperature or voltage drop. Refer
to local wiring regulations for the correct size of cables.
Table 12-26 Size 4 and larger input current, fuse and cable size ratings
Cable sizes are from IEC60364-5-52:2001 table A.52.C with correction
factor for 40°C ambient of 0.87 (from table A52.14) for cable installation
method B2 (multicore cable in conduit).
Only PVC insulated cables should be used.
Cable size may be reduced if a different installation method is used, or if
the ambient temperature is lower.
The recommended cable sizes above are only a guide. The mounting
and grouping of cables affects their current-carrying capacity, in some
cases smaller cables may be acceptable but in other cases a larger
cable is required to avoid excessive temperature or voltage drop. Refer
to local wiring regulations for the correct size of cables.
Inrush current
The drive will have an inrush current during power-up, the peak inrush is
limited to the value shown below:
BA120X
18 A peak
BA140X
35 A peak
BA220X
12 A peak
BA240X
24 A peak
BA320X
8 A peak
BA340X
14 A peak
BA350X
18 A peak
For sizes 4 to 6, the inrush current is limited by a controlled rectifier to
below the rated current of the drive.
The inrush current for all drives after a brown-out can be larger than the
power-up inrush.
NOTE
Model
Typical input
current
Maximum
input current
Fuse option 1
Fuse option 2
semiconductor fuse in series
with HRC fuse or breaker
Cable size
IEC class
gR
North
America:
Ferraz HSJ
HRC
IEC class gG
UL class J
Semi-
conductor
IEC class aR
EN60204
UL508C
A
A
A
A
A
A
Input
mm
2
Output
mm
2
Input
AWG
Output
AWG
BA
4201
62.1
68.9
100
90
90
160
25
25
3
3
BA
4202
72.1
78.1
100
100
100
160
35
35
3
3
BA
4203
94.5
99.9
125
125
125
200
70
70
1
1
BA
5201
116
142
200
175
160
200
95
95
2/0
2/0
BA
5202
137
165
250
225
200
250
120
120
4/0
4/0
BA
4401
61.2
62.3
80
80
80
160
25
25
3
3
BA
4402
76.3
79.6
100
110
100
200
35
35
2
2
BA
4403
94.1
97.2
125
125
125
200
70
70
1
1
BA
5401
126
131
200
175
160
200
95
95
2/0
2/0
BA
5402
152
156
250
225
200
250
120
120
4/0
4/0
BA
6401
224
241
315
300
250
315
2 x 70
2 x 70
2 x 2/0
2 x 2/0
BA
6402
247
266
315
300
300
350
2 x 95
2 x 95
2 x 4/0
2 x 4/0
BA
4601
23
26.5
63
60
32
125
4
4
10
10
BA
4602
26.1
28.8
63
60
40
125
6
6
8
8
BA
4603
32.9
35.1
63
60
50
125
10
10
8
8
BA
4604
39
41
63
60
50
125
16
16
6
6
BA
4605
46.2
47.9
63
60
63
125
16
16
6
6
BA
4606
55.2
56.9
80
60
63
125
25
25
4
4
BA
5601
75.5
82.6
125
100
90
160
35
35
2
2
BA
5602
89.1
94.8
125
100
125
160
50
50
1
1
BA
6601
128
138
200
200
200
200
2 x 50
2 x 50
2 x 1
2 x 1
BA
6602
144
156
200
200
200
200
2 x 50
2 x 50
2 x 1
2 x 1
NOTE
NOTE