Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
132
Affinity User Guide
www.controltechniques.com Issue Number: 5
If Pr
11.37
is set to 1002 the checksum parameter (Pr
11.40
) shows the
state of the read-only (bit 0) and warning suppression flags (bit 1).
If Pr
11.37
is set to 1003, the checksum parameter (Pr
11.40
) shows the
product identifier (255 = Unidrive SP, 1 = Commander GP20, 2 = Digitax
ST, 3 = Affinity).
If there is no data on the card Pr
11.37
can only have values of 0 or 1000
to 1003.
9.4 SMARTCARD parameters
Table 9-3 Key to parameter table coding
This parameter shows the number of the data block last transferred from
a SMARTCARD to the drive.
This parameter should have the data block number entered for which the
user would like information displayed in Pr
11.38
, Pr
11.39
and Pr
11.40
.
Gives the type/mode of the data block selected with Pr
11.37
:
Gives the version number of the data block selected in Pr
11.37
.
Gives the checksum of the data block selected in Pr
11.37
.
N
If Pr
11.42
is equal to 1 or 2, this value is not transferred to the drive or
saved to the EEPROM. If Pr
11.42
is set to a 3 or 4 the value is
transferred.
nonE (0) = Inactive
rEAd (1) = Read parameter set from the SMARTCARD
Prog (2) = Programming a parameter set to the SMARTCARD
Auto (3) = Auto save
boot (4) = Boot mode
RW
Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not copied
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save
11.36 {0.29}
SMARTCARD parameter data previously loaded
RO
Uni
NC
PT
US
Ú
0 to 999
Ö
0
11.37
SMARTCARD data number
RW
Uni
NC
Ú
0 to 1003
Ö
0
11.38
SMARTCARD data type/mode
RO
Txt
NC
PT
Ú
0 to 18
Ö
Pr 11.38
String
Type/mode
Data stored
0
FrEE
Value when Pr
11.37
= 0, 1000 to
1003
1
Reserved
2
3OpEn.LP
Open-loop mode parameters
Data from
EEPROM
3
3 rfc
RFC mode parameters
4
Reserved
5
Reserved
6 to 8
3Un
Unused
9
Reserved
10
4OpEn.LP
Open-loop mode parameters
Defaults last
loaded and
differences
11
4 rfc
RFC mode parameters
12
Reserved
13
Reserved
14 to 16
4Un
Unused
17
LAddEr
Onboard PLC program
18
Option
A Solutions Module file
11.39
SMARTCARD data version
RW
Uni
NC
Ú
0 to 9,999
Ö
0
11.40
SMARTCARD data checksum
R0
Uni
NC
PT
Ú
0 to 65,335
Ö
11.42 {0.30}
Parameter copying
RW
Txt
NC
US*
Ú
0 to 4
Ö
nonE (0)
NOTE
Summary of Contents for Affinity
Page 274: ...0474 0000 05 ...