Parameter
Range(
Ú
)
Default(
Ö
)
Type
OL
RFC
OL
RFC
4.01
Total motor current
{
0.12
}
0 to DRIVE_CURRENT_MAX A
RO Uni FI NC PT
4.02
Active current
±DRIVE_CURRENT_MAX A
RO
Bi
FI NC PT
4.03
Torque demand
±TORQUE_PROD_CURRENT_MAX %
RO
Bi
FI NC PT
4.04
Current demand
RO
Bi
FI NC PT
4.05
Motoring current limit
0 to MOTOR1_CURRENT_LIMIT_MAX %
110
RW Uni
RA
US
4.06
Regen current limit
RW Uni
RA
US
4.07
Symmetrical current limit
{
0.06
}
RW Uni
RA
US
4.08
Torque reference
±USER_CURRENT_MAX %
0.00
RW
Bi
US
4.09
Torque offset
0.0
RW
Bi
US
4.10
Torque offset select
OFF (0) or On (1)
OFF (0)
RW Bit
US
4.11
Torque mode selector
0 to 1
0
RW Uni
US
4.12
Current demand filter 1
{
0.17
}
0.0 to 25.0 ms
0.0
RW Uni
US
4.13
Current controller Kp gain
0 to 30,000
20
200V drive: 75
400V drive: 150
575V drive: 180
690V drive: 215
RW Uni
US
4.14
Current controller Ki gain
40
200V drive: 1000
400V drive: 2000
575V drive: 2400
690V drive: 3000
RW Uni
US
4.15
Thermal time constant
0.0 to 3000.0
89.0
RW Uni
US
4.16
Thermal protection mode
0 to 1
0
RW Bit
US
4.17
Reactive current
±DRIVE_CURRENT_MAX A
RO
Bi
FI NC PT
4.18
Overriding current limit
±TORQUE_PROD_CURRENT_MAX %
RO Uni
NC PT
4.19
Overload accumulator
0 to 100.0 %
RO Uni
NC PT
4.20
Percentage load
{
0.13
}
±USER_CURRENT_MAX %
RO
Bi
FI NC PT
4.22
Inertia compensation enable
OFF (0) or On (1)
OFF (0)
RW Bit
US
4.23
Current demand filter 2
0.0 to 25.0 ms
0.0
RW Uni
US
4.24
User current maximum scaling
0.0 to TORQUE_PROD_CURRENT_MAX
%
110
RW Uni
RA
US
4.25
Low speed thermal protection
mode
OFF (0) or On (1)
On (1)
RW Bit
US
4.26
Percentage torque
±USER_CURRENT
_MAX %
RO
Bi
FI NC PT
4.27
Low load detection level
{
0.26
}
0.0 to 100.0 %
0.0
RW
US
4.28
Low level detection speed /
frequency threshold
{
0.27
}
0.0 to ±SPEED_FREQ_MAX Hz/rpm
0.0
RW
US
4.29
Trip in abnormal load detection
{
0.28
}
OFF (0) or On (1)
OFF (0)
RW Bit
US
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not copied
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save