Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
Affinity User Guide
119
Issue Number: 5 www.controltechniques.com
7.4.2 RFC mode
Induction motor
Run
Drive is now ready to run
Action
Detail
Action
Detail
Before power-
up
Ensure:
•
Drive Enable signal is not given (terminal 31)
•
Run signal is not given
•
Motor and feedback device are connected
Power-up the
drive
Verify that Closed Loop mode is displayed as the drive powers up. If the mode is incorrect see Chapter
7.2
If a motor thermistor is not connected and the drive trips on ‘th’ set Pr
0.21
= VOLt and press the red
reset button.
Ensure:
• Drive displays ‘inh’
• Set the drive to closed loop vector mode. See Chapter 7.2
for more information.
If the drive trips, see Chapter 13
Enter motor
nameplate
details
Enter:
•
Motor rated frequency in Pr
0.47
(Hz)
•
Motor rated current in Pr
0.46
(A)
•
Motor rated speed (base speed - slip speed) in Pr
0.45
(rpm)
•
Motor rated voltage in Pr
0.44
(V) - check if or connection
Set maximum
speed
Enter:
•
Maximum speed in Pr
0.02
(rpm)
Set acceleration
/ deceleration
rates
Enter:
•
Acceleration rate in Pr
0.03
(s/1000rpm)
•
Deceleration rate in Pr
0.04
(s/1000rpm) (If braking resistor installed, set Pr
0.15
= FAST. Also
ensure Pr
10.30
and Pr
10.31
are set correctly, otherwise premature ‘It.br’ trips may be seen.)
Select or
deselect catch a
spinning motor
mode
If catch a spinning motor mode is not required then set Pr
6.09
to 0.
If catch a spinning motor mode is required then leave Pr
6.09
at the default of 1, but depending on the
size of the motor the value in Pr
5.40
may need to be adjusted.
Pr
5.40
defines a scaling function used by the algorithm that detects the speed of the motor. The default
value of Pr
5.40
is 1 which is suitable for small motors (<4kW). For larger motors the value in Pr
5.40
will need to be increased. Approximate values of Pr
5.40
for different motor sizes are as follows, 2 for
11kW, 3 for 55kW and 5 for 150kW. If the value of Pr
5.40
is too large the motor may accelerate from
standstill when the drive is enabled. If the value of this parameter is too small the drive will detect the
motor speed as zero even if the motor is spinning.
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55 I.cl F C 40 s S1
°
V
Hz min
-1
kW cos
φ
A
230
400
50 1445 2.20 0.80 8.50
4.90
CN = 14.5Nm
240
415
50 1445 2.20 0.76 8.50
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
I.E
.C
34
1(
87
)
0.02
t
1000rpm
0.03
t
0.04
Summary of Contents for Affinity
Page 274: ...0474 0000 05 ...