SM-I/O Plus parameters
*See trip SLX.Er,
Automation (I/O Expansion) module category
Parameter
Range(
Ú
)
Default(
Ö
)
Type
x.01
Solutions Module ID
0 to 599
201
RO Uni
PT US
x.03
T4 digital I/O 3 state
OFF (0) or On (1)
RO Bit
NC PT
x.04
T6 digital input 4 state
RO Bit
NC PT
x.05
T7 digital input 5 state
RO Bit
NC PT
x.06
T8 digital input 6 state
RO Bit
NC PT
x.07
Relay 1 state
RO Bit
NC PT
x.08
Relay 2 state
RO Bit
NC PT
x.09
T2 digital I/O 1 state
RO Bit
NC PT
x.10
T3 digital I/O 2 state
RO Bit
NC PT
x.11
T2 digital I/O 1 invert
OFF (0)
RW Bit
US
x.12
T3 digital I/O 2 invert
RW Bit
US
x.13
T4 digital I/O 3 invert
RW Bit
US
x.14
T6 digital input 4 invert
RW Bit
US
x.15
T7 digital input 5 invert
RW Bit
US
x.16
T8 digital input 6 invert
RW Bit
US
x.17
Relay 1 invert
RW Bit
US
x.18
Relay 2 invert
RW Bit
US
x.20
Digital I/O read word
0 to 511
RO Uni
NC PT
x.21
T2 digital I/O 1 source/
destination
Pr
0.00
to Pr
50.99
Pr
0.00
RW Uni DE
PT US
x.22
T3 digital I/O 2 source/
destination
RW Uni DE
PT US
x.23
T4 digital I/O 3 source/
destination
RW Uni DE
PT US
x.24
T6 digital input 4 destination
RW Uni DE
PT US
x.25
T7 digital input 5 destination
RW Uni DE
PT US
x.26
T8 digital input 6 destination
RW Uni DE
PT US
x.27
Relay 1 source
RW Uni
PT US
x.28
Relay 2 source
RW Uni
PT US
x.29
Input polarity select
OFF (0) or On (1)
On (1) (positive logic)
RW Bit
PT US
x.31
T2 digital I/O 1 output select
OFF (0)
RW Bit
US
x.32
T3 digital I/O 2 output select
RW Bit
US
x.33
T4 digital I/O 3 output select
RW Bit
US
x.40
Analog input 1
±100.0%
RO Bi
NC PT
x.41
Analog input 1 scaling
0 to 4.000
1.000
RW Uni
US
x.42
Analog input 1 invert
OFF (0) or On (1)
OFF (0)
RW Bit
US
x.43
Analog input 1 destination
Pr
0.00
to Pr
50.99
Pr
0.00
RW Uni DE
PT US
x.44
Analog input 2
±100.0%
RO Bi
NC PT
x.45
Analog input 2 scaling
0.000 to 4.000
1.000
RW Uni
US
x.46
Analog input 2 invert
OFF (0) or On (1)
OFF (0)
RW Bit
US
x.47
Analog input 2 destination
Pr
0.00
to Pr
50.99
Pr
0.00
RW Uni DE
PT US
x.48
Analog output 1 source
RW Uni
PT US
x.49
Analog output 1 scaling
0.000 to 4.000
1.000
RW Uni
US
x.50
Solutions Module error status*
0 to 255
RO Uni
NC PT
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not copied
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save
Summary of Contents for Affinity