A1120/1140 Programmable Polyphase Meter Users Manual
___________________________________________________________________
3.4.8
Meter Constants
Transformer Ratios
The A1120/40 Meter can be supplied for the following types of connection:
Direct connected or CT operated.
The screen shows connection for a CT operated meter.
The maximum CT Ratio is 500:1
Performing a Billing Reset on CT Ratio Change
Check the panel to perform a billing reset when the meter CT Ratio is changed.
CT Ratio Display
The meter can display the CT as a ratio or as a scalar quantity. Check the panel to display as a CT
Ratio. Leave unchecked to display as scalar.
CT Error
The CT error can be compensated for.
To compensate for a CT error of +0.4%, enter a value of +0.4%, then a compensation value of -0.4%
will be applied.
Note:
If the CT programming switch is fitted to the meter, the switch must be activated in order to
change the CT ratio.
3.4.9 Relay
Setup
The pulsing output of the A1120/40 meter can be configured to one of the following options:
Retransmit
Rate indication
Retransmit
Retransmit is selected along with the appropriate Source,
Pulse value and the Pulse width.
Ensure that the chosen pulse value and pulse width leaves adequate gaps between pulses at
maximum meter loads.
©
Elster Metering Ltd - M181 001 3C - 12/2007
Summary of Contents for A1120
Page 2: ......
Page 3: ...A1120 40 Programmable Electronic Polyphase Meter Chapter 1 Introduction M181 001 1B 5 2009 ...
Page 4: ...Minor Change Record Date Modification 7 5 2009 Format change ...
Page 8: ......
Page 53: ...Operating Maintenance Instructions 45 Figure 4 Load Curves ...
Page 70: ......
Page 71: ......
Page 73: ......
Page 91: ......
Page 156: ......