5.12 Mains Lack Time
•
It is possible to program the mains lack time (timeout) before the event
is sent via communicator. It is programmable with steps of 2 minutes,
1 hour, 2 hours, 4 hours. The mains return timeout is fixed at 2÷3
minutes.
1. Enter the engineer’s code
2. To access the procedure, press key
EXIT
F
+ key
A
twice.
3. The display will show the current value (see side table). By key
1
choose the desired value (0-1-2-4).
4. By pressing key
EXIT
F
, you quit the programming and the chosen status
is taken. When quitting by timeout, the previously stored status will be
kept.
•
If the arming is made from keypad, the self-bypassing is properly
signalled on the display. The arming regularly takes place and no alarm
is generated. The self-bypassed zones are reentered automatically at
their re-closing (even with armed system).A following opening will
therefore generate the alarm.
NOTE:
In case of arming with electromechanical key or remote via Fast Link, the
Commutating Lock and Self-bypassing functions are not considered even
if programmed. The arming will take place in any case and in case of open
zones an alarm will be generated.
1.
Enter the engineer’s code
2.
To access the procedure, press key
EXIT
F
and key
O
twice.
3.
The display will show the current value from 0 to 9 (see side table).
By means of the numeric keys choose the desired value (0-9).
4.
Press key
O
to enable/disable the commutating lock with
open zones.
5.
Press key E to enable/disable open zone by-passing.
6.
By pressing key
EXIT
F
, you quit the programming and the chosen
status is taken. When quitting by timeout, the previously stored status
will be kept.
00 = count disabled
01 = 1 alarm
02 = 2 alarms
03 = 3 alarms
04 = 4 alarms
05 = 5 alarms
06 = 6 alarms
07 = 7 alarms
08 = 8 alarms
09 = 9 alarms
•
The
led shows the pro-
gramming of the commutating
lock with open zones.
LED on= commutating lock ena-
bled
LED off= commutating lock disa-
bled
•
The
led shows the pro-
gramming of the open zone self-
bypassing
LED on= self-bypassing enabled
LED off= self-bypassing disa-
bled
PROCEDURE ACCESS
COD.
1/3
F
A
F
0 = 2 minutes
1 = 1 hour
2 = 2 hours
4 = 4 hours
56