21 Analog input module XN-322-7AI-U2PT
21.5 Technical data for reference outputs
152
XN300 slice modules
06/16 MN050002 EN
www.eaton.com
21.5 Technical data for reference outputs
21.6 Measurement ranges
21.7 Filters
The low-pass cutoff frequency can be configured for each voltage input chan-
nel by using the appropriate register. This cutoff frequency is specified in Hz
without any decimal places.
The following settings are valid:
Device version
1.00 or higher
3.01 or higher
Number of channels
1
Connection points per channel
6
Reference voltage
+10 V
Permissible load per
potentiometer input
Max. permissible output current
≤
2.50 mA
≤
4.17 mA
Potentiometer
≥
4 k
Ω
≥
2.4 k
Ω
Maximum operating temperature
0…60 °C
0…55 °C
Maximum permissible capacitive
load
100 nF
Short-circuit proof
Yes, maximum 1 minute
Cumulative error as a percentage of
full scale value
±0.3 %
Input 1
Value representation
1
U
-10…+10 V
Represented as a decimal value in mV
Pt1000
-125…+850 °C
502.4…3904.8
Ω
Represented as a decimal value in
ohms with one decimal place (in 1/10
ohm)
KTY10
-50…+150 °C
1035.9…4575.3
Ω
2-6
U
-10…+10V
-10000…10000
Represented as a decimal value in mV
7
Pt1000
-125…+850 °C
502.4…3904.8
Ω
Represented as a decimal value in °C
with one decimal place (in 1/10 °C)
KTY10
-50…+150 °C
1035.9…4575.3
Ω
Low-pass cut-off frequency
Register value
Filter disabled (default)
0x0000
10 Hz
0x000A
25 Hz
0x0019
50 Hz
0 x0032
100 Hz
0x0064
Summary of Contents for XN300