25 Analog input/output module ±10 V XN-322-4AIO-U2
25.5 Filters
188
XN300 slice modules
06/16 MN050002 EN
www.eaton.com
25.5 Filters
The low-pass cutoff frequency can be individually configured for each input
channel using the appropriate register. This cutoff frequency is specified in
Hz without any decimal places.
Example: 50 Hz low-pass cutoff frequency; register value: 50
dec
/ 32
hex
The following settings are valid:
25.6 Technical Data
25.6.1 Analog inputs ±10 V / 0…100%
Low-pass cut-off frequency
Register value
Filter disabled (default)
0x0000
10 Hz
0x000A
25 Hz
0x0019
50 Hz
0x0032
100 Hz
0x0064
250 Hz
0x00FA
500 Hz
0x01F4
1000 Hz
0x03E8
Number of channels
2
Measurement type
Differential input
Potentiometer input
Measuring range
V
-10 V ...+10 V
0 …100 % (potentiometer)
Measurement display
-10,000 ... +10,000
0 ... 10,000
D-A converter
Bit
16
Resolution
0.3 mV / LSB
Conversion time per channel
ms
1
Common-mode range
V
±12
Input resistance
M
> 10
Open wire monitoring
yes
Input filters
Hardware
Typically: 1 kHz, third-order low-pass filter
Software, parameterizable
parameterizable
Cumulative error as a
percentage of full scale value
%
±0.3
±0.35