27 Analog input/output module XN-322-4AIO-I
27.4 Technical data
206
XN300 slice modules
06/16 MN050002 EN
www.eaton.com
Two analog outputs for a burden resistance of less than 500
Ω
can be wired
to connector X2.
0 < R
burden
< 500
Ω
Figure 112:
Connecting example showing signal current sources at X1 and burden current
sources at X2
27.4 Technical data
27.4.1 Analog inputs
X1
1+ 1- 2+ 2-
X2
1+ -
2+ -
X3
PE
24 V
0 V
+
-
+
-
F1
I
max
24V 24V 0V 0V
Channels
Value
Number of channels
2 analog input channels
Measuring range
0…20 mA
Measured value
0…20000
D-A converter
16 Bit
Resolution
0.3
μ
A/ LSB
Conversion time per channel
1 ms
Common-mode range
± 10 V
Input resistance
50
Ω
Input filters
Hardware
typically 1 kHz (third-order low-pass filter)
Software (parameterizable)
parameterizable
Open wire monitoring
Yes
Measuring accuracy
Total error limit
±0.5% of full scale value