28 XN-322-8AIO-I analog input/output module
28.3 Wiring
216
XN300 slice modules
06/16 MN050002 EN
www.eaton.com
28.3 Wiring
Two analog inputs can be wired to each of the two X1 and X2 connectors. A
measuring range of 4–20 mA with cable break monitoring is supported, as is
a measuring range of 0–20 mA without cable break monitoring.
The current input channels use a differential voltage measurement at an
internal module resistor with a resistance of 50
Ω
.
It must be ensured that the input signals' voltage levels fall within the per-
missible common mode range.
Two analog outputs for a burden resistance of less than 500
Ω
can be wired
to connector X2.
0 < R
burden
< 500
Ω
Figure 116:
Connecting example showing signal current sources at X1, X2 and burden cur-
rent sources at X3, X4
28.4 Technical data
28.4.1 Analog inputs
X1
1+ 1- 2+ 2-
X2
X3
X4
X5
3+ 3- 4+ 4-
3+ -
4+ -
PE
24 V
0 V
+
-
+
-
+
-
+
-
24V 24V 0V 0V
1+ -
2+ -
F1
I
max
R
Bürde
R
Bürde
Channels
Value
Number of channels
4 analog input channels
Measuring range
0…20 mA
4…20 mA
Measured value
0…20000
4000…20000
D-A converter
16 Bit
Resolution
0.3
μ
A/ LSB
Conversion time per channel
1 ms
Common-mode range
± 10 V
Input resistance
50
Ω
Input filters
Hardware
typically 1 kHz (third-order low-pass filter)
Summary of Contents for XN300
Page 4: ...II...