22 Analog input module XN-322-8AI-I
22.4 Technical data
XN300 slice modules
06/16 MN050002 EN
www.eaton.com
163
0x5090
2
Measuring range parameter
configuration
Bit 0 (AI1)
0: measurement range
0…20mA
1: measurement range
4…20mA
Bit 1 (AI2)
0: measurement range
0…20mA
1: measurement range
4…20mA
Bit 2 (AI3)
0: measurement range
0…20mA
1: measurement range
4…20mA
Bit 3 (AI4)
0: measurement range
0…20mA
1: measurement range
4…20mA
Bit 4 (AI5)
0: measurement range
0…20mA
1: measurement range
4…20mA
Bit 5 (AI6)
0: measurement range
0…20mA
1: measurement range
4…20mA
Bit 6 (AI7)
0: measurement range
0…20mA
1: measurement range
4…20mA
Bit 7 (AI8)
0: measurement range
0…20mA
1: measurement range
4…20mA
Bit 8-15
reserved
0x5091
2
Setting for AI1 input filter
Used to specify the cutoff
frequency as a decimal value
in Hz.
0x5092
2
Setting for AI2 input filter
0x5093
2
Setting for AI3 input filter
0x5094
2
Setting for AI4 input filter
0x5095
2
Setting for AI5 input filter
0x5096
2
Setting for AI6 input filter
0x5097
2
Setting for AI7 input filter
0x5098
2
Setting for AI8 input filter
CAN Object
Index
Size
(byte)
Description
Summary of Contents for XN300
Page 4: ...II...
Page 14: ...10 XN300 slice modules 06 16 MN050002 EN www eaton com...