205
5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
Group
Parameter
Number
Name
Setting Range
Factory
Value
User
settings
10-26
P.237
Amplitude compensa-
tion for acceleration
0~50.0%
10.0%
10-27
P.238
Amplitude
acceleration time
0~360.00s/0~3600.0s
10.00s
10-28
P.239
Amplitude
deceleration time
0~360.00s/0~3600.0s
10.00s
10-29
P.247
MC switchover
interlock time
0.1~100.0s
1.0s
10-30
P.248
Start waiting time
0.1~100.0s
0.5s
10-31
P.249
Switchover frequency
from inverter to
commercial power
supply frequency
0~60.00Hz
99999
99999: No automatic switchover order.
10-32
P.250
Automatic switchover
frequency range
0~10.00Hz: When the inverter start reference (STF/STR) is
turned off after the operation is changed from inverter opera-
tion to commercial power supply operation, the operation will
be changed to the inverter operation.
99999
99999: When the inverter start reference (STF/STR) is turned
off after the operation is changed from inverter
operation to commercial power supply operation, the
operation will be changed to the inverter operation
and the motor will decelerate until it stops.
10-33
P.273
Power failure stop
selection
0: Power failure time deceleration-to-stop
function disabled.
0
1: No undervoltage avoidance (Ifan undervoltage or power
failureoccurs, the motordecelerates to a stop.)
2: No undervoltage avoidance (If an undervoltage or power
failure occurs, the motor decelerates to a stop. Motor
re-accelerates if the power restores during the decelera-
tion to stop.)
11: Undervoltage avoidance (If an undervoltage or power
failure occurs, the motor decelerates to a stop.)
12: Undervoltage avoidance (If an undervoltage or power
failure occurs, the motor decelerates to a stop. Motor
re-accelerates if the power restores during the decelera-
tion to stop.)
10-34
P.274
Subtracted frequency
at deceleration start
0~20.00Hz
3.00Hz
10-35
P.275
Subtraction starting
frequency
0~120.00Hz: When output frequency
≥
10-35(P.275), The motor
decelerates from the “output frequency - 10-34(P.274)”; When
output frequency<10-35(P.275), deceleration from output fre-
quency
50.00Hz
99999: The motor decelerates from the “output frequency -
10-34(P.274)”
10-36
P.276
Power-failure decel-
eration time 1
0~360.00s/0~3600.00s
5.00s
10-37
P.277
Power-failure decel-
eration time 2
0~360.00s/0~3600.00s: Set the Dec time starting at10-38(P.278)
anddownward.
99999
99999: Set the Dec time to the setting frequency of 10-
38(P.278).