186
5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
Group
Parameter
Number
Name
Setting Range
Factory
Value
User
settings
08-24
P.711
PID target signal filter time
0~650.00s
0.00s
08-25
P.712
PID feedback signal filter time
0~60.00s
0.00s
08-26
P.713
PID output signal filter time
0~60.00s
0.00s
08-27
P.714
PID deviation control limit
0~100.00%
0.00%
08-28
P.715
Integral separated property
0: Integral not separated
0
1: Integral separated
08-29
P.716
Integral separated point
0~100.00%
50.00%
08-30
P.717
PID differential limit
0~100.00%
0.10%
08-31
P.718
PID output in forward directionde-
viation limit
0~100.00%
100.0%
08-32
P.719
PID output in reverse direction
deviation limit
0~100.00%
100.0%
08-33
P.720
PID parameter switchover opera-
tion selection
0: No PID parameter switchover.
0
1: PID parameter switchover based ondeviation.
08-34
P.721
PID parameter switchover
deviation lower limit
0~100.00%
20.00%
08-35
P.722
PID parameter switchover
deviation upper limit
0~100.00%
80.00%
08-36
P.723
PID wire-break operation selec-
tion1
0: When PID wire-break, select to no need to operate to
the upper limit value.
1
1: When PID wire-break, select to need to operate to the
upper limit value.
08-39
P.726
PID operation at stop
0: No PID operation at stop.
0
1: PID Stop operation
08-40
P.727
PID enable reverse run operation
0: PID reverse run is not allowed.
0
1: PID reverse run is allowed.
08-41
P.728
PID in reverse direction integral
limit
0~100.0%
0.0%
08-42
P.729
PID minimum output frequency
0~10.00Hz
0.00Hz