5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
Group
Parameter
Number
Name
Setting Range
Factory
Value
User
settings
07-16
P.801
CAN open speed
3: 125Kbps
0
4: 100Kbps
5: 50 Kbps
07-17
P.802
CAN open communi-
cation status
0: Node reset state
0
1: Com reset state
2: Boot up state
3: Pre operation state
4: Operation state
5: Stop state
07-18
P.803
CAN open control
status
0: Not ready for use state
0
1: Inhibit start state
2: Ready to switch on state
3: Switched on state
4: Enable operation state
7: Quick stop active state
13: Err reaction activation state
14: Error state
07-25
P.810
PU Communication
protocol selection
0: Modbus protocol
1
1: Eaton protocol
2: PLC protocol (Effective when using the Eaton built-in PLC)
07-26
P.811
PU converter stations
0~254
0
07-27
P.812
PU Serial communica-
tion baud rate
0: Baud rate 4800bps
1
1: Baud rate 9600bps
2: Baud rate 19200bps
3: Baud rate 38400bps
4: Baud rate 57600bps
5: Baud rate 115200bps
07-28
P.813
PU data length
0: 8bit
0
1: 7bit
07-29
P.814
PU stop bit
0: 1bit
0
1: 2bit
07-30
P.815
PU Parity check option
0: no odd-even check
0
1: odd check
2: even check
07-31
P.816
PU CR/LF choose
1: only CR
1
2: CR, LF Both
07-32
P.817
PU Modbus
communication
format
0: 1, 7, N, 2 (Modbus, ASCII)
4
1: 1, 7, E, 1 (Modbus, ASCII)
2: 1, 7, O, 1 (Modbus, ASCII)
3: 1, 8, N, 2 (Modbus, RTU)
4: 1, 8, E, 1 (Modbus, RTU)
5: 1, 8, O, 1 (Modbus, RTU)