174
5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
Mode
Start
Address*1)
Function*2)
Start Address*3)
Write-in data*4)
Check
Stop
ASCII
H3A
2char
2char
4char
4char
2char
0D 0A
RTU
>=10ms
8bit
8bit
2byte
2byte
2byte
>=10ms
Message
Content
*1) Address
Set up the address for the to-be delivered message.
*2) Function code
H06
*3) Starting address
Set up the starting address of the register to be engaged in the write-in function.
*4) Write-in data
Write the data in the assigned register. The data have to be 16bit (fixed).
ote:
N
Regular response content and the inquired message are the same.
3. Write multiple registers (H10)
Mode
Start
Address*1)
Function*2)
Start Ad-
dress*3)
Number of
register *4) Data*5) Write-in data *6)
Check
Stop
ASCII
H3A
2char
2char
4char
4char
2char
4char
…2N×8bit
2char
0D 0A
RTU
>=10ms
8bit
8bit
2byte
2byte
1byte
2byte
…N×16bit
2byte
>=10ms
Regular response
Mode
Start
Address*1)
Function*2) Start Address*3) Number of register *4)
Check
Stop
ASCII
H3A
2char
2char
4char
4char
2char
0D 0A
RTU
>=10ms
8bit
8bit
2byte
2byte
2byte
>=10ms
Message
Content
*1) Address
Set up the address for the to-be delivered message.
*2) Function code
H10
*3) Starting address
Set up the starting address of the register to be engaged in the write-in function.
*4) Number of register
Set up the number of register for reading. Maximum number: 20.
*5) Amount of data
The range should be 2 ~ 24. Set Twice the amount of *4).
*6) Write-in data
Set the assigned data in *4), write the data according to the sequence of the Hi byte and the Lo byte and the
data of the starting address: According to the order of the data of the starting a1, data of the starting
a2…, etc.
4. Function Diagnosis (H08)
By sending query information and getting the same query information back (the function of the subroutine code H00),
it can do communication calibration.
The subroutine code H00 (for inquiring the return of data)
The query information
Mode
Start
Address*1)
Function*2)
Subroutine *3)
Data *4)
Check
End
ASCII
H3A
2char
2char
4char
4char
2char
0D 0A
RTU
>=10ms
1byte
1byte
2byte
2byte
2byte
>=10ms