5. Parameter Description
5.1 System parameter group 00
Group
Parameter
Number
Name
Setting Range
Factory
Value
User
settings
00-00
P.90
The inverter model
Read
read
00-01
P.188
Firmware version
Read
read
00-02
P.996~P.999
Parameter restoration
0: Non-function
0
1: Alarm history clear (P.996=1)
2: Inverter reset (P.997=1)
3: Restoring all parameters to default values (P.998=1)
4: Restoring some parameters to default values1 (P.999=1)
5: Restoring some parameters to default values2 (P.999=2)
6: Restoring some parameters to default values3 (P.999=3)
00-03
P.77
Selection of
parameterswrite protection
0: Parameters can be written only when the motor stops
0
1: Parameters cannot be written
2: Parameters can also be written when the motor is
running
3: Parameters cannot be written when in password
protection
00-04
P.294
Decryption parameter
0~65535
0
00-05
P.295
Password setup
2~65535
0
00-06
P.110
Parameter unit monitoring
selection
X0: When the inverter starts, the parameter unit enters the
monitoring mode automatically, and the screen displays the
output frequency
1
X1: When the inverter starts, the screen of the parameter
unit displays the target frequency
X2: When the inverter starts, the parameter unit enters the
monitoring mode automatically, and the screen displays
the current pressure and feedback pressure of the constant
pressure system
0X: Boot screen to monitor model output frequency
1X: Boot screen to set the target frequency mode
2X: Boot screen to monitor model of output current
3X: Boot screen to monitor mode of the output voltage
00-07
P.161
Multi-function display
0: Output voltage (V)
0
1: Inverter voltage between (+/P) and (-/N) terminals (V)
2: Temperature rising accumulation rate of inverter (%)
3: Target pressure of the constant pressure system (%)
4: Feedback pressure of the constant pressure system (%)