179
5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
Item
Eaton pro-
tocol
reference
code
Modbus
reference
code
Modbusaddress Data content and function description
Parameter delete
HFC
H06/
H10
H1104
H5A5A
For details,
please refer
to the param-
eter restoration
status table.
H5566
H5959
H1103
H9966
H1106
H9696
H99AA
H9A9A
H1105
H55AA
H1102
HA5A5
Parameter read-out
H00~H63
H03
P mode:
H0000~H0513
Parameter group
mode:
H2710~H2D4F
1.
The data range and the position of the decimal
point, please refer to the parameter table..
2.
In P mode, the Modbus address of each param-
eter corresponds to the hexadecimal digit of the
parameter number. For example, the Modbus
address of 04-26(P.138) is H008A.
3.
In parameter group mode, the Modbus address
of each parameter corresponds tothe parameter
the hexadecimal digit of 10000, such as
the Modbus address of04-26(P.138) is 0x28BA.
Parameter write-in
H80~HE3
H06/
H10
Line speed feedback read-out
---
H03
H100A
H0000~HFDE8
Line speed feedback write-in
H06/H10
Line speed target value read-out
---
H03
H100B
H0000~HFDE8
Line speed target value write-in
H06/H10
Tension reference read-out
---
H03
H100C
H0000~H7530
Tension reference write-in
H06/H10
Torque reference read-out
---
H03
H100D
H0000~H0FA0 (0~400.0%)
HF060~HFFFF (-400.0%~0)
Torque reference write-in
H06/H10
Loopback test for asynchronous
serial communication
---
H08
H0000 (sub
function code for
loopback test)
The content value is arbitrary (H0000~HFFFF)
Operation reference write-in
HFA
H06/
H10
H1001
H0000~HFFFF
b8~b15: reserve.
b7: inverter emergency stop (MRS)
b6: the second function (RT)
b5: high speed (RH)
b4: medium speed (RM)
b3: low speed (RL)
b2: reverse rotation (STR)
b1: forward rotation (STF)
b0: reserve.