5.3.5 Selection and handling of input terminal AI1
• Selects the signal specifications, frequency compensation function, and input signalpolarity, etc, viainput terminal AI1.
Parameter
Name
Factory
Value
Setting Range
Content
02-08
P.73
AI1 signal selection
1
0
The valid range of signal sampling is 0~5V.
1
The valid range of signal sampling is 0~10V.
2
The valid range of signal sampling is 0~ -5V.
3
The valid range of signal sampling is 0~ -10V.
4
The valid range of signal sampling is -5~ +5V.
5
The valid range of signal sampling is -10~ +10V.
02-09
P.38
AI1 maximumoperation
frequency
50.00Hz
1.00~650.00Hz
50Hz system (00-24=1)
60.00Hz
60Hz system (00-24=0)
02-10
P.60
AI1 filter time
30ms
0~2000ms
---
02-11
P.139
The bias rate of AI1 voltage
signal
0.0%
-100.0%~
100.0%
---
02-12
P.192
The minimum input positive
voltage of AI1
0.00V
0~10.00V
---
02-13
P.193
The maximum input positive
voltage of AI1
10.00V
0~10.00V
---
02-14
P.194
The percentage correspond-
ing to the minimum positive
voltage of terminal AI1
0.0%
-100.0%~100.0%
---
-400.0%~400.0%
(P.500= 2/14/15/16/17)
02-15
P.195
The percentage correspond-
ing to the maximum posi-
tive voltage of terminal AI1
100.0%
-100.0%~100.0%
---
-400.0%~400.0%
(P.500= 2/14/15/16/17)
02-16
P.512
The minimum input nega-
tive voltage of AI1
0.00V
0~10.00V
---
02-17
P.513
The maximum input nega-
tive voltage of AI1
0.00V
0~10.00V
---
02-18
P.510
The percentage correspond-
ing to the minimum nega-
tive voltage of termianl AI1
0.0%
-100.0%~100.0%
---
-400.0%~400.0%
(P.500= 2/14/15/16/17)
02-19
P.511
The percentage correspond-
ing to the maximum nega-
tive voltage of termianl AI1
0.0%
-100.0%~100.0%
---
-400.0%~400.0%