5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
5.3.2 Function selection of analog output terminal AM
• Selects the data to be output via analog output terminal AM.
Usage of analog output terminal AM
•
For the voltage/current calibration of terminal AM, please refer to calibration parameter in Section 5.3.11Selection
and handling of output terminal AO1.
Parameter
Name
Factory
Value
Setting Range
Content
02-04
P.54
Function of terminal
AO1 output
0
0
Output frequency, the frequency display reference 02-51 (P.55) is 100%.
1
Output frequency, the frequency display reference 02-52 (P.56) is 100%.
2
Output DC bus voltage, the OV level is 100%.
3
Output the temperature rising accumulation rate of inverter, the NTC level
is 100%.
4
Output the electronic thermal rate of the inverter, the electronic thermal
relay running (06-00(P.9)
≠
0) or the electronic thermal relay of the inverter’s
IGBT module running (06-00(P.9)=0) is 100%.
5
Target frequency, the frequency display reference 02-51 (P.55) is 100%.
6
Fixed level output, voltage or current output level is set by 02-54 (P.541)
/02-53 (P.539)
7
Output voltage, the inverter rated voltage is 100%.
8
Excitation current, the motor rated current is 100%. (Valid only when 00-
21 (P.300) or 00-22 (P.370) is set to 3~6).
9
Output torque, two times motor rated torque is100%. (Valid only when
00-21 (P.300) or 00-22 (P.370) is set to 3~6)
10
Output power, two times motor rated power is 100%.
11
The high-speed pulse, 100.00KHz is 100%.
12
Motor speed, to display the level of 02-51 (P.55) is 100%.
13
PLC analog output, details please refer to DF1 embedded PLC instructions
02-05
P.537
Function of terminal
AO2 output
0
0~13
6: Steady level output, voltage or current output level is set by 02-53
(P.539).
0~5, 7~13: Same as 02-04.