97
5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
5.3.6 Selection and handling of input terminal AI3
• Selects the signal specifications, frequency compensation function, etc, via input terminal AI3.
Selection and handling of input terminal AI3
•
AI3 signal selection and the maximum operation frequency of terminal AI3
Parameter
Name
Factory
Value
Setting Range
Content
02-20
P.17
AI3 signal selection
0
0
The effective range of signal sampling is 4~20mA.
1
The effective range of signal sampling is 0~10V.
2
The effective range of signal sampling is 0~5V.
02-21
P.39
The maximum operation
frequency of terminal AI3
50.00Hz
1.00~650.00Hz
50Hz syetem (00-24=1)
60.00Hz
60Hz syetem (00-24=0)
02-22
P.528
AI3 filter time
30ms
0~2000ms
---
02-23
P.505
The bias rate of AI3
current/voltage signal
0.0%
-100.0%~100.0% ---
02-24
P.184
AI3 disconnection selection
0
0
No disconnection selection is available.
1
Decelerate to 0Hz, the digital output terminal will set off the
alarm
2
The inverter will stop immediately, and the panel willdisplaythe
“AEr” alarm.
3
The inverter will run continuously according to the frequency
reference before the disconnection. The digital output terminal
will set off the alarm.
02-25
P.198
The minimum input current/
voltage of terminal AI3
4.00mA
0~20.00mA
---
02-26
P.199
The maximum input current
/voltage of terminal AI3
20.00mA
0~20.00mA
---
02-27
P.196
The percentage correspond-
ing to the minimum input
current/voltage of
terminal AI3
0.0%
-100.0%~100.0% ---
-400.0%~400.0% (P.501= 2/14/15/16/17)
02-28
P.197
The percentage correspond-
ing to the maximum input
current/voltage of
terminal AI3
100.0%
-100.0%~100.0% ---
-400.0%~400.0% (P.501= 2/14/15/16/17)