181
5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
Item
Eaton
protocol
reference
code
Modbus
reference
code
Modbusad-
dress
Data content and function description
Page change for
parameter reading
and writing
Write
Read
H7F
---
---
H006D: 09-00~09-99
H006E: 10-00~10-99
H006F: 11-00~11-99
H0070: 12-00~12-99
H0071: 13-00~13-99
H0072: 14-00~14-99
H0073: 15-00~15-99
HFF
Monitoring
Frequency setup
EEPROM
H73
H6D
H03
H1008
H1009
H1002
H0000~HFDE8 (two decimal points when 00-08=0; one decimal
point when non-zero)
RAM
Output frequency
H6F
H1003
H0000~H9C40(same as above)
Output current
H70
H1004
H0000~HFFFF (two decimal points)
Output voltage
H71
H1005
H0000~HFFFF (two decimal points)
Abnormal content
H75
H74
H1007
H0000~HFFFF: Abnormal codes from the last two times
H74/H1007: Error code 1 and 2;
b15 b8 b7 b0
H75/H1008: Error code 3 and 4;
b15 b8 b7 b0
For abnormal codes, please refer to the abnormal code list in
the abnormal record parameter06-40~06-43.
Error code 2
Error code 1
Error code 4
Error code 3
Data
content
Parameter
Poperation
Communication
Parameter P (Note 1)
Table 1
(Note2)
Table 2
(Note2)
User registered
parameter
Other P
parameters
Error codes
H5A5A
00-02=4 (P.999=1)
o
x
x
o
o
x
H5566
00-02=5 (P.999=2)
o
x
o
x
o
x
H5959
00-02=6 (P.999=3)
o
x
x
x
o
x
H9966
00-02=3 (P.998=1)
o
x
o
o
o
x
H9696
Communication 999 1 x
x
x
o
o
x
H99AA
Communication 999 2 x
x
o
x
o
x
H9A9A
Communication 999 3 x
x
x
x
o
x
H55AA
Communication 998
x
x
o
o
o
x
HA5A5
00-02=1 (P.996=1)
x
x
x
x
x
o
ote:
N
1. Communication P parameters includes 07-02(P.32), 07-00(P.33), 07-01(P.36), 07-03(P.48)~ 07-09(P.53), 00-16(P.79), 07-10(P.153)
and 07-07(P.154).
2. For the table 1 and table 2, please refer to Section 5.1.2.