144
5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
Group
Parameter
Number
Name
Setting Range
Factory
Value
User
settings
06-13
P.281
Input phase failure protection
0: No Phase Failure Protection
0
1: Phase failure protection, the parameter unit will
display the “IPF” alarm and the output stops.
06-14
P.287
SCP Short circuit protection
function
0: No the output end short-circuits protection function.
1
1: If outputend is short, the parameter unit will display
the “SCP” alarm and the output stops.
06-15
P.533
The process mode of PTC alarm
0: Alarm and continue to run
0
1: Alarm and decelerate to stop
2: Alarm and stop freely
3: No alarm
06-16
P.534
The percentage of PTC level
0~100.0%
0.0%
06-17
P.261
Maintenance alarm function
0: No maintenance alarm
0
1~9998day: Used to set time whenmaintenancealarm
sends out signal
06-18
P.280
Short circuit detection when
starting
0: No short circuit detection when starting
0
1: Short circuit detection when starting
06-19
P.282
Operation GF detection level
280K/315KF types below: 0~100.0%
50.0%
315K/355KF type: 0~100.0%
70.0%
06-20
P.262
Output phase failure protection
0: No output phase failure protection selection
0
1: Output phase failure protection, the parameter unit
will display the “LF” abnormal alarm and the invert-
er will stop the output.
06-21
P.705
Low voltage level
155~220V: 220V inverter type
155V
310~440V: 440V inverter type
310V
06-22
P.706
Regenerative brake operation
level
205~400V: 220V inverter type
360V
410~800V: 440V inverter type
720V
06-23
P.707
Voltage stall level
205~400V: 220V inverter type
380V
410~800V: 440V inverter type
760V
06-24
P.708
Capacitor lifetime detection
0: No capacitor lifetime detection.
0
06-24
P.708
Capacitor lifetime detection
1: When the power is OFF, start to detect the lifetime of
electrolytic capacitor on main circuit.
0
06-25
P.709
Capacitor lifetime detection
level
0~100.0%
100.0%
06-26
P.710
Capacitor lifetime detection
result
0: No abnormal signal.
Read
1: Electrolytic capacitor abnormal.
06-27
P.292
Accumulative motor operation
time (minutes)
0~1439min
0min
06-28
P.293
Accumulative motor operation
time (days)
0~9999day
0day
06-29
P.296
Accumulative motor power time
(minutes)
0~1439min
0min
06-30
P.297
Accumulative motor power time
(days)
0~9999day
0day
06-40
P.288
Alarm code query
0~12
1