For example: assuming 01-16=45 and 01-17=50;
If the target frequency
≤
45Hz, then the steady output frequency=the target frequency.
If 45Hz
≤
target frequency=50Hz, then the steady output frequency=45Hz.
If the target frequency
≥
50Hz, then the steady output frequency=the target frequency.
ote:
N
1. During the acceleration / deceleration period, the output frequency of the inverter will still pass through the jump frequency.
2. When 01-16=99999 or 01-17=99999, the first set of frequency jump is invalid.
When 01-18=99999 or 01-19=99999, the second set of frequency jump is invalid.
When 01-20=99999 or 01-21=99999, the third set of frequency jump is invalid.
5.2.10 The second function
• It is appropriate for the parameters when the RT signal is ON.
The second function
•
When 01-08=0, minimum acceleration / deceleration time(01-22, 01-23)increment is0.01s.
•
When 01-08=1, minimum acceleration / deceleration time(01-22, 01-23)increment is0.1s.
•
When RT is “on”, the second function is valid. For the operation characteristics of the motor, please refer to the fol-
lowing second function setting.
If 01-22
≠
99999 and 01-23=99999, when RT is “on”, the acceleration /deceleration time is the “set value of 01-22”.
If 01-22
≠
99999 and 01-24=99999, when RT is “on”, the torque boost is the “set value of 01-10”.
If 01-22
≠
99999 and 01-24
≠
99999, when RT is “on”, the torque boost is the “set value of01-24”.
If 01-22
≠
99999 and 01-25=99999, when RT is “on”, the base frequency isthe “set value of 01-03”.
If 01-22
≠
99999 and 01-25
≠
99999, when RT is “on” the base frequency is the “set value of 01-25”.
ote:
N
RT metioned here is the function name of “multi-function digital input terminal”. Please refer to 03-00~03-05/
P.80~P.84,P.86, 03-06(P.126), 03-09 (P.550) for the function selection of multi-function digital input terminal; please refer to
Section 3.3 for related wiring.
01-16
(P.91)
01-17
(P.92)
01-18
(P.93)
01-19
(P.94)
01-20
(P.95)
01-21
(P.96)
Output
frequency
(Hz)
Parameter
Name
Factory
Value
Setting Range
Content
01-22
P.44
The second acceleration time
99999
0~360.00s/
0~3600.0s
01-08=0/
01-08=1
99999
Not selected.
01-23
P.45
The second deceleration time
99999
0~360.00s/
0~3600.0s
01-08=0/
01-08=1
99999
Not selected.
01-24
P.46
The second torque boost
99999
0~30.0%
---
99999
Not selected.
01-25
P.47
The second base frequency
99999
0~650.00Hz
---
99999
Not selected.