Settings
Contextual help of the web interface – 136
•
•
•
•
•
•
•
•
•
•
•
•
•
•
d Test trap
Press the Test trap button to send the trap test to all trap receivers.
Separate window provides the test status with following values:
In progress
Request successfully sent
invalid type
3.7.8.3 Link to SNMP traps
3.7.8.4 Default settings and possible parameters - SNMP
Default setting
Possible parameters
SNMP
Activate SNMP — disabled
Port — 161
SNMP V1 — disabled
Community #1 — public
Enabled — Inactive
Access — Read only
Community #2 — private
Enabled — Inactive
Access — Read/Write
SNMP V3 — enabled
User #1 — readonly
Enabled — Inactive
Access — Read only
Authentication — Auth (SHA-1)
Password — empty
Confirm password — empty
Privacy — Secured - AES
Key — empty
Confirm key — empty
User#2 — readwrite
Enabled — Inactive
Access — Read/Write
Authentication — Auth (SHA-1)
Password — empty
Confirm password — empty
Privacy — Secured - AES
Key — empty
Confirm key — empty
Activate SNMP — disable/enable
Port — x-xxx
SNMP V1 — disable/enable
Community #1 — 128 characters maximum
Enabled — Inactive/Active
Access — Read only
Community #2 — 128 characters
maximum
Enabled — Inactive/Active
Access — Read/Write
SNMP V3 — disable/enable
User #1 — 32 characters maximum
Enabled — Inactive/Active
Access — Read only/Read-Write
Authentication — Auth (SHA-1)/None
Password — 128 characters maximum
Confirm password — 128 characters
maximum
Privacy — Secured - AES/None
Key — 128 characters maximum
Confirm key — 128 characters maximum
User#2 — 32 characters maximum
Enabled — Inactive/Active
Access — Read only/Read-Write
Authentication — Auth (SHA-1)/None
Password — 128 characters maximum
Confirm password — 128 characters
maximum
Privacy — Secured - AES/None
Key — 128 characters maximum
Confirm key — 128 characters maximum
For details on SNMP trap codes, see the
section.
Summary of Contents for Network-M3
Page 1: ...UPS Network Management Card Network M3 User s Guide English 10 27 2023...
Page 2: ......
Page 10: ...Table of Contents 10 Applicable product Eaton UPS ATS...
Page 32: ...Home Contextual help of the web interface 32 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode...
Page 34: ...Home Contextual help of the web interface 34 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode...
Page 36: ...Home Contextual help of the web interface 36 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode...
Page 63: ...Protection Contextual help of the web interface 63 Example 2 Immediate OFF...
Page 64: ...Protection Contextual help of the web interface 64 Example 4 Custom Settings 1...
Page 120: ...Settings Contextual help of the web interface 120 3 7 6 3 SSH 3 7 6 4 SNMP 3 7 6 5 MQTT...
Page 287: ...Acronyms and abbreviations Information 287...
Page 294: ......