SNMP traps
Information – 267
Trap oid :
.1.3.6.1.4.1.534.1.11
.4.1.0.x
Trap message at
oid :
.1.3.6.1.4.1.534.1.1
1.3.0
Code HID (For UPS 5P, 5PX, 9SX,
9PX, 9xPM, 9xE, 9xPS)
Code XCP (For UPS Blade,
9395, 9395P, 9395C, 9x55)
.1.3.6.1.4.1.534.1.11
.4.1.0.
11
Bypass mode
205
2169
.1.3.6.1.4.1.534.1.11
.4.1.0.
12
Bypass not available 201
2105, 2003, 2004, 2142, 2005
.1.3.6.1.4.1.534.1.11
.4.1.0.
13
Load not powered
819, 81A, 818, 81D
2170
.1.3.6.1.4.1.534.1.11
.4.1.0.
14
On battery
104, 106
2067, 2006, 2007, 2008, 2059
.1.3.6.1.4.1.534.1.11
.4.1.0.
15
Building alarm
through input dry
contact
110
2014, 2015, 2016, 2017, 2018,
2019, 2370, 2371, 2372
.1.3.6.1.4.1.534.1.11
.4.1.0.
16
Shutdown
imminent
2055
.1.3.6.1.4.1.534.1.11
.4.1.0.
17
No more on bypass
205
.1.3.6.1.4.1.534.1.11
.4.1.0.
20
Breaker open
103, 204, 606
2106, 2107, 2108, 2109, 2137,
2251, 2252, 2254, 2255, 2252
.1.3.6.1.4.1.534.1.11
.4.1.0.
23
Battery test failed
607, 61B
2149, 2191, 2247
.1.3.6.1.4.1.534.1.11
.4.1.0.25
Diagnostic test
failed
2053, 2064, 2079, 2176
.1.3.6.1.4.1.534.1.11
.4.1.0.
26
Communication lost 005
.1.3.6.1.4.1.534.1.11
.4.1.0.
30
Sensor contact is
active
.1.3.6.1.4.1.534.1.11
.4.1.0.
31
Sensor contact back
to normal
.1.3.6.1.4.1.534.1.11
.4.1.0.
32
Parallel UPS
redundancy lost
00B
2132
.1.3.6.1.4.1.534.1.11
.4.1.0.
33
Temperature alarm
004, 203, 501, 605, 706
1201, 1204, 2202, 2203, 2200,
2020, 2021, 2024, 2073, 2111,
2201, 2223, 2249
.1.3.6.1.4.1.534.1.11
.4.1.0.
34
Battery charger
fault
500
2030, 2022, 2034, 2075, 2076,
2208, 2259, 2260, 2261
.1.3.6.1.4.1.534.1.11
.4.1.0.
35
Fan fault
007
2193
.1.3.6.1.4.1.534.1.11
.4.1.0.
36
Fuse fault
100, 600, 602, 701
2192
.1.3.6.1.4.1.534.1.11
.4.1.0.
42
Sensor temperature
is below/above
critical threshold
Summary of Contents for Network-M3
Page 1: ...UPS Network Management Card Network M3 User s Guide English 10 27 2023...
Page 2: ......
Page 10: ...Table of Contents 10 Applicable product Eaton UPS ATS...
Page 32: ...Home Contextual help of the web interface 32 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode...
Page 34: ...Home Contextual help of the web interface 34 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode...
Page 36: ...Home Contextual help of the web interface 36 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode...
Page 63: ...Protection Contextual help of the web interface 63 Example 2 Immediate OFF...
Page 64: ...Protection Contextual help of the web interface 64 Example 4 Custom Settings 1...
Page 120: ...Settings Contextual help of the web interface 120 3 7 6 3 SSH 3 7 6 4 SNMP 3 7 6 5 MQTT...
Page 287: ...Acronyms and abbreviations Information 287...
Page 294: ......