Configuring the SNMP Settings
The SNMP Settings page allows you to enable and disable SNMP communication
between an SNMP manager and the ePDU. Enabling SNMP communication allows
the ePDU to send SNMP trap events to the manager, and allow the manager to
retrieve and control the power status of each outlet.
To configure SNMP communication (necessary for passing SNMP traps and individual
outlet control):
1.
Select
Device Settings
, and then select
SNMP Settings
. The SNMP Settings page
displays.
Figure 78. SNMP Settings Page
2.
Select the
Enable SNMP Agent
check box to enable the ePDU to communicate
with external SNMP managers. A number of options will then become available.
3.
Select the
Enable SNMP v1 / v2c Protocol
check box to enable communication with
an SNMP manager using SNMP v2c protocol.
4.
Type the SNMP read−only community string in the
Read Community
field
5.
Type the read/write community string in the
Write Community
field.
6.
Select the
Enable SNMP v3 Protocol
check box to enable communication with an
SNMP manager using SNMP v3 protocol.
7.
Type the system location in the
System Location
field.
8.
Type the system contact in the
System Contact
field.
9.
Click the link at the bottom of the page to download an SNMP MIB for your
ePDU to use with your SNMP manager.
10.
Click
Apply
. The SNMP configuration is set.
Summary of Contents for Managed ePDU
Page 1: ...Managed ePDU User s Guide...
Page 4: ......
Page 10: ...TABLE OF CONTENTS EATON Managed ePDUt User s Guide S 164201xxx Rev 1 DRAFT 10 OCT 2008 vi...
Page 16: ...SAFETY WARNINGS EATON Managed ePDUt User s Guide S 164201xxx Rev 1 DRAFT 10 OCT 2008 6...
Page 20: ...RACK MOUNTING THE EPDU EATON Managed ePDUt User s Guide S 164201xxx Rev 1 DRAFT 10 OCT 2008 10...
Page 128: ......
Page 129: ...164201xxx1 164201xxx 1...