USING THE IPMI TOOL SET
EATON
Managed ePDU
t
User’s Guide
S
164201xxx Rev 1
DRAFT 10−OCT−2008
105
Test Sensors
Used for hardware testing during production.
Request Data
1
–
Response Data
1
Completion Code
2
[7–2] reserved
[1] down button, 0b = not pressed, 1b = pressed
[0] up button, 0b = not pressed, 1b = pressed
Set Power Cycle Delay Command
Request Data
1
Socket number (0xFF for the global unit delay)
2
Delay (seconds), 1–255 for unit and socket, 0 fallback to the unit delay
(socket only)
Response Data
1
Completion Code
Get Power Cycle Delay Command
Request Data
1
Socket number (0xFF for the global unit delay)
Response Data
1
Completion Code
2
Delay (seconds), 1–255, 0 if not set (socket only)