USING THE EPDU
EATON
Managed ePDU
t
User’s Guide
S
164201xxx Rev 1
DRAFT 10−OCT−2008
21
LED Display
The LED display panel is located adjacent to the outlets on the 0U model, and on the
back right of the 1U and 2U models. Figure 21 shows the LED display.
Figure 21. LED Display Panel
The LED display panel consists of these components:
S
A top row that displays three digits
S
A bottom row that displays two digits
S
UP and DOWN buttons
NOTE
The small hole between the lower row and the Down button is the Reset hole. The ePDU can be
reset to its factory default values through this hole only when connected to the serial port. See the Resetting
to Factory Defaults" section on page 17 for additional configuration details. Pressing the Reset button ONLY
restarts the ePDU.
Lower Row:
The lower row shows the outlet number.
Upper Row:
The upper row shows the current, voltage, and power readings for the
outlet indicated in the lower row. During the firmware upgrade process, the upper
row displays ˆFuP˜ to indicate that a Firmware Upgrade is being performed on the
ePDU.
How to Operate the Display Panel:
S
Use the Up and Down buttons to select an outlet. Pressing the Up button once
moves up one outlet number. Pressing the Down button once moves down one
outlet number.
S
When an outlet is selected, the outlet number is displayed in the lower row and
the current in the upper row. Current is displayed in the format: XX.X (A).
S
To display the voltage for the selected outlet, press the Up and Down buttons
simultaneously. The voltage reading will replace the current for about 5 seconds,
after which the current will return.
S
To display the active power for the selected outlet, first press the Up and Down
buttons simultaneously to display the voltage, and then again to display the active
power. Active Power is displayed in the format: X.XX in volt−amps (VA).
NOTE
Tip:
A quick way to distinguish between voltage, current, and power is the placement of the
decimal point in the display. Voltage has no decimal point, current has a decimal point between the first and
second digits, and power has a decimal point between the second and third digits.
Summary of Contents for Managed ePDU
Page 1: ...Managed ePDU User s Guide...
Page 4: ......
Page 10: ...TABLE OF CONTENTS EATON Managed ePDUt User s Guide S 164201xxx Rev 1 DRAFT 10 OCT 2008 vi...
Page 16: ...SAFETY WARNINGS EATON Managed ePDUt User s Guide S 164201xxx Rev 1 DRAFT 10 OCT 2008 6...
Page 20: ...RACK MOUNTING THE EPDU EATON Managed ePDUt User s Guide S 164201xxx Rev 1 DRAFT 10 OCT 2008 10...
Page 128: ......
Page 129: ...164201xxx1 164201xxx 1...