4. External connections
4. External connections
With its ports, Eaton's RTD makes it possible to connect a variety of peripheral
devices and components.
DANGER
STRAY CURRENTS
Large equalizing currents between the functional earthing system
and the ground system of different devices may result in fire or in mal-
functions due to signal interference.
If necessary, route an equipotential bonding conductor, with a
cross-sectional area that is several times larger than that of the
cable shielding, parallel to the cable.
CAUTION
INTERFERENCES
The values specified in the technical data, as well as the device's
electromagnetic compatibility (EMC), cannot be guaranteed if the fol-
lowing are used: unsuitable cables, improperly assembled and ter-
minated cables, and/or wiring that does not conform to the applicable
standards.
Only use cables assembled and terminated by professionals.
The cables being used must be assembled and terminated as
required by the port/interface description in this document.
When wiring the RTD, follow all instructions regarding how to wire
the corresponding port/interface.
All general Directives and standards must be complied with.
easyE Remote Touch Display
01/24 MN048027EN Eaton.com
51
Summary of Contents for easyE
Page 1: ...Manual 01 24 MN048027EN easyE Remote Touch DisplayManual...
Page 4: ......
Page 8: ...8 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Page 14: ...0 1 About this documentation 14 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Page 26: ...1 Description 1 10 Marine approvals 26 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Page 54: ...4 External connections 4 2 Ethernet 54 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Page 88: ...7 Operation 7 2 Device menus 88 easyE Remote Touch Display 01 24 MN048027EN Eaton com...