3. Installation
3.6 Preparing the device for operation
Electrical connection
0 V
+24 VDC
Fig. 11: Power supplied via plug connector
Use the plug-in connection to terminate the connection cable for the power sup-
ply in advance.
Plug the pre-assembled plug connector into the socket on the enclosure.
Pay attention to the polarity "+24V" and "0V".
Connect the power supply cable to a 24 VDC power supply (-20%/+25%) that
meets the requirements for safety extra-low voltages (SELV) set forth in IEC
60950 and – in connection with the UL listing – the requirements for a low-
voltage source set forth in UL 61010-2-201, UL61010-1.
The easyE Remote Touch Display is now ready to run on 24 VDC.
easyE Remote Touch Display
01/24 MN048027EN Eaton.com
49