3. Installation
3.1 Prerequisites for the location of use
3.1.1 Installation position
The following must be taken into account when selecting the installation position:
l
The size of the installation cutout depends on the device type:
EASY-RTD-DC-43-...: e = 123 mm (4.84") ± 0,5 mm (0.02"), f = 87 mm (3.43") ± 0,5 mm
(0.02")
e
f
d
α
α
l
Make sure that the material at the installation location is sufficiently thick
Material thickness of 2 mm (0.08") ≦ d ≦ 5 mm (0.2")
and flatness of
≦ 0.5 mm (0.02") at the installation cutout with a surface rough-
ness
Rz ≦ 120; IP 65 → DIN ISO 2768-2 (K)
l
The controls and connectors must remain accessible even after the device has
been installed.
l
If no forced ventilation is being used, the device must not be mounted at an angle
exceeding α max. ± 90°.
l
No direct sunlight on the device.
CAUTION
UV LIGHT
Plastics will become brittle when exposed to UV light. This artificial
aging will reduce the RTD unit's lifespan.
Protect the Resistive Touch Display unit from direct sunlight and
other sources of UV radiation.
l
Make sure that the RTD does not overheat.
l
The minimum clearance to components that radiate heat, such as transformers
under heavy loads, is 15 cm.
easyE Remote Touch Display
01/24 MN048027EN Eaton.com
37
Summary of Contents for easyE
Page 1: ...Manual 01 24 MN048027EN easyE Remote Touch DisplayManual...
Page 4: ......
Page 8: ...8 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Page 14: ...0 1 About this documentation 14 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Page 26: ...1 Description 1 10 Marine approvals 26 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Page 54: ...4 External connections 4 2 Ethernet 54 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Page 88: ...7 Operation 7 2 Device menus 88 easyE Remote Touch Display 01 24 MN048027EN Eaton com...