Connection parts for marathon
®
gas burners with pneumatic linkage
dreizler A 3001 E - 18.12.2015 | A 2053 - 1.15 | EN - 18.05.2015
96
30 Connection parts for marathon
®
gas burners with pneumatic link-
age
30.1 Connection parts betw. burner head and gas ramp with gas controls CG15-30
NOTICE:
Verify correct control line connections during installation (see pos. 10 + 11)!
The correct position of the air impulse tap P (9) at the swirl plate is in flow direction, see Fig. 30-1 "Connec-
tion parts CG 15 - 30"
- the burner sizes M 121 up to M 3001 on 10:00 - 11:00 o’clock position
- the burner sizes M 5001.1, M 5001 and M 5001.4 on 3:00 o’clock position
Other positions may cause a nonlinear control behaviour of the pneumatic gas/air linkage (nonlinear
adjustment of the oxygen content in the exhaust gas)!
Fig. 30-2 Example for position P
Air
for M 121 up to M 3001
Fig. 30-1 Connection parts CG 15 - 30
1 burner head
2 flame tube
3 burner housing
4 Schott push-on connector
5 Schott push-on connector
6 hose
7 hose
8 pipe
9 pipe
10 hose
P
f
pressure combustion chamber
black
11 hose
P
L
air blue
12 gas control unit
13 quick coupling piece
14 gas ramp
15 plug nipple
16 swivel plate