Settings for burner with electronic linkage
dreizler A 3001 E - 18.12.2015 | A 2041 - 3.14 | EN - 11.11.2014
34
NOTICE:
Afterwards, fill out the test report accordingly see chapter 51 "Measuring report and calculations" for details.
11.8 Configuring the combustion manager BurnerTronic BT 3xx
A detailed operating manual for the combustion manager BurnerTronic BT 3xx is included in the appendix.
Please read the operations manual carefully before commissioning the system.
11.8.1 Doweling of servomotor and oil regulator in the type BT 3xx
In dual fuel burners of the version oil modulating with directly to the burner mounted oil regulator,
the coupling of the servomotor and the oil regulator must be doweled and pinned after commission-
ing.
The servomotor has a working range of 0 to 90°. The oil regulator (1) and the servomotor (2) shall be
doweled so, that a maximum output of the burner to max position is possible. (The pin (9) is included
and attached in a lose manner.)
Fig. 11-2 Servomotor attachment
1
Oil regulator 24 VK 1
2
Servomotor BT 340
3
Retaining plate for servomotor
4
Distance bolt
5
Washer
6
Cylinder head screw
7
Threaded pin
8
Hex number
9
Dowel pin with slot (coupling pinned with regulator)
10 Coupling
WARNING!
The 230V-voltage at the input of the boiler safety sequence and the supply voltage of the combustion man-
ager BT 3xx must have the same phase.
Due to a voltage breakdown different phases can lead to serious consequences for the combustion
manager and the installation.