Safety instructions
dreizler A 3001 E - 18.12.2015 | A 2000 - 1.13 | EN - 03.05.2013
11
The components of the gas ramp of the burner must be protected with the attachment of a bezel during
pressure checks of system components.
Please note data provided on the type plate of the burner for max. supply pressure. Ensure strict com-
pliance with this max. value.
NOTICE:
Notes and information regarding warranty cover
Possible loss of warranty!
Defective burner components must only be replaced by members of the service team. Unilateral repair
work or any opening of the units is prohibited and will result in a loss of warranty.
Storage temperatures of -25°C to +50°C and operating temperatures of -10°C to +45°C are mandatory.
marathon
®
gas and dual fuel burners are certified to a maximum of 90°C combustion air temperature
and are approved for operation. Higher temperatures on request.
The burner may only be operated in a clean and dry environment and must be free of vibration and
noise.
We can provide you with the max. values for sulphur content in combustion gas on request.
Please note the nominal life expectancy data on safety components and replacement intervals for wear
parts (see chapter A 2006 'Annual inspection and maintenance').
System maintenance must be carried out by authorised technicians at least every 12 months or every
4000 operating hours.
NOTICE:
Store the operations manual and burner identity card in a safe place.
This manual must be freely available to all operations technicians at all times.
The scope of delivery and accessory parts for the burner, as well as all important burner data is listed on
the burner identity card.