Air pressure switch
dreizler A 3001 E - 18.12.2015 | A 2029 - 2.14 | EN - 11.11.2014
132
40.3.2 marathon
®
burner - model with parameter 'frequency'
Burner size
Model
frequency
Air pressure switch
Configuration
range
Air pressure switch
type
Factory configuration
Dungs
121
0.5 - 5 mbar
LGW 10 A2
1.0 mbar
201
0.5 - 5 mbar
LGW 10 A2
3.0 mbar
301
1.0 - 10 mbar
LGW 10 A2
4.1 mbar
601
1.0 - 10 mbar
LGW 10 A2
depending on
system conditions
1001
1.0 - 10 mbar
LGW 10 A2
depending on
system conditions
1501
1.0 - 10 mbar
LGW 10 A2
depending on
system conditions
2001
1.0 - 10 mbar
LGW 10 A2
depending on
system conditions
3001
1.0 - 10 mbar
LGW 10 A2
depending on
system conditions
5001.1
1.0 - 10 mbar
LGW 10 A2
depending on
system conditions
5001
1.0 - 10mbar
LGW 10 A4
depending on
system conditions
10001
2.5 - 50mbar
LGW 50 A4
depending on
system conditions
10003
2.5 - 50mbar
LGW 50 A4
depending on
system conditions