Basic configuration of burner controller RWF40
dreizler A 3001 E - 18.12.2015 | A 2069 - 1.09 | EN - 21.10.2009
149
Return to standard display by pressing 'EXIT', or wait 30 seconds (time-out).
47.1.3 Changing the configuration (configuration level) based on the standard display.
1) Press button 'PGM' 2x for at least 2 seconds.
2) Setpoint display shows 'C 111' (analog inputs).
3) Use key 'q' to select the digit for changing the code. This is signalled with
a blinking display.
4) Press key 'p' to reconfigure the digit.
5) Wait 2 seconds, then the value is saved automatically.
6) Press button 'PGM' shortly, and 'C 112' is shown (limit comparator, controller type).
7) Repeat setting procedure as for C 111.
8) Press button 'PGM' shortly, and 'C 113' is shown (device address, unit).
9) Repeat setting procedure as for C 111 and C 112.
10) Press button 'PGM' shortly several times.
11) The setpoint display shows 'SPL'.
12) Use the keys 'pq' to enter the lower setpoint limit.
13) Wait 2 seconds, then the value is saved automatically.
14) Press button 'PGM' shortly, 'SPH' is displayed.
15) Use the keys 'pq' to enter the upper setpoint limit.
16) Wait 2 seconds, then the value is saved automatically.
Return to standard display by pressing 'EXIT', or wait 30 seconds (time-out).
NOTICE:
The controller must be set to manual operation to conduct the burner test. Press the button 'EXIT' for at
least 5 seconds.
Run time SA
t t
- 30
Burner activation
HYS 1
- -3,0
Deactivation 2nd step
HYS 2
- 3,0
Burner deactivation
HYS 3
- 5,0
Code 111 without external sensor
9 0 0 0
Code 111 with external sensor
9 0 3 0
Code 112 without external sensor
0 0 0 0
Code 112 with external sensor
0 0 1 0
Code 113
0 1 1 0
Lower setpoint limit
SPL
- 53,0
Upper setpoint limit
SPH
- 85,0