Servomotor type SQM 5...
dreizler A 3001 E - 18.12.2015 | A 2027 - 2.14 | EN - 11.11.2014
61
18.2 Preadjustment of the servomotor SQM 5...
The following drawings show the allocation of the switching cams of servomotor SQM 5... on the example
SQM 54 anti-clockwise rotation model in delivery condition ex works.
Tab. 18-1 Example: Setting the switching cams for SQM 54... anti-clockwise rotation
Switching position cam I at MAX (full load)
Limit switch switches at MAX load 90° between 1
and 11 to throughput.
Switching position cam II, zero position of air damper
Limit switch switches at switching point approx. 0°
between 2 and 22 to throughput.
Switching position cam II at ignition load
Limit switch switches at ignition load at 40°
between 3 and 23 to throughput.
Switching position cam IV at MIN (small load)
Limit switch switches at MIN load approx. 30°
between 4 and 24 to throughput.