Basic configuration of burner controller RWF40
dreizler A 3001 E - 18.12.2015 | A 2069 - 1.09 | EN - 21.10.2009
151
47.2.3 Changing the configuration (configuration level) based on the standard display
1) Press button 'PGM' 2x for at least 2 seconds.
2) Setpoint display shows 'C 111' (analog inputs).
3) Use key 'q' to select the digit for changing the code. This is signalled by a blinking display.
4) Press key 'p' to reconfigure the digit.
5) Wait 2 seconds, then the value is saved automatically.
6) Press button 'PGM' shortly, and 'C 112' is shown (limit comparator, controller type).
7) Repeat setting procedure as for C 111.
8) Press button 'PGM' shortly, and 'C 113' is shown (device address, unit).
9) Repeat setting procedure as for C 111 and C 112.
10) Press button 'PGM' shortly several times.
11) The setpoint display shows 'SCL'.
12) Use the keys 'pq' to enter the min. pressure for the pressure range set at 0 V.
13) Wait 2 seconds, then the value is saved automatically.
14) Press button 'PGM' shortly, 'SCH' is displayed.
15) Use the keys 'pq' to enter the max. presure for the pressure range set at 10 V.
16) Wait 2 seconds, then the value is saved automatically.
Return to standard display by pressing 'EXIT', or wait 30 seconds (time-out).
configuration example: Pressure sensor QBE 620-P10 (0 - 10 bar)
NOTICE:
The controller must be set to manual operation to conduct the burner test. Press the button 'EXIT' for at
least 5 seconds.
NOTICE:
Use the keys 'pq' to let the burner modulate. In burners with two-step operation, ensure that the selected
command is permanently set.
Run time SA
t t
- 30
Burner activation
HYS 1
- -1,0
Deactivation 2nd step
HYS 2
- 1,0
Burner deactivation
HYS 3
- 1,5
Code 111 without external sensor
G 0 0 0
Code 112
0 0 0 0
Code 113
0 1 1 0
Scaling low
SPL
- 0,0
Scaling high
SPH
- 10,0