Ignition and flame monitoring of gas burners marathon
®
M...
dreizler A 3001 E - 18.12.2015 | A 2009 - 1.15 | EN - 05.02.2015
67
19.2.2 Ignition with pilot burner
Fig. 19-5 Front view - burner head with pilot burner
Fig. 19-6 Side view - burner head with ignition gas burner
1
Gas nozzle
2
Ignition electrodes
3
Stabilising disc
4
Ignition gas pipe
The ignition gas burner must be set in such a way that a stable ignition flame is created.
Setting the ignition gas burner.
Ignition gas pipe adjust 10 - 20mm downstream of the stabilisation disk.
Setting pre-throttling at the ignition gas valve.
The flame must remain on the stabilising disc and must not lift off.