Configurable Safety System SAFEMASTER PRO
42
0265525 / 16.05.19 en / 101A
INPUT MODULE UG 6913.08 AND UG 6913.16
INPUT MODULE UG 6913.12
Type:
UG 6913.08
UG 6913.16
SFF:
(IEC 61508: 2
nd
edition)
99.7 %
99.7 %
PFH
d
:
4.45E-9
4.94E-9
MTTF
d
:
EN ISO 13849-1: 2008
473.00
396.47
DC
avg
:
99.0 %
99.0 %
Nominal voltage:
24 V DC
±
20 % / PELV, PREDective Class III; UL: Supply from class 2 (LVLE)
Nominal consumption:
Max. 3 W
Inrush current:
Max. 7 A, 0.3 ms
Digital safety inputs (No. / description):
8
16
„Type 2“ acc. to EN 61131-2 IN: 7 to 10 mA at DC 24 V
Inputs for Node selection NODE_SEL0/1
(No. / description):
2 / „Type 2“ acc. to EN 61131-2 IN: 7 to 10 mA at DC 24 V
Test output (No. / description):
4 / to check for short-circuits - overloads
max. number of inputs for each output:
2
4
Connection to control unit:
Proprietary 5-pole DOLD IN-RAIL-BUS
Weight:
190 g
Approvals:
SFF:
(IEC 61508: 2
nd
edition)
99.7 %
PFH
d
:
5.56E-9
MTTF
d
:
EN ISO 13849-1: 2008
326.05
DC
avg
:
99.0 %
Nominal voltage:
24 V DC
±
20 % / PELV, PREDective Class III; UL: Supply from class 2 (LVLE)
Nominal consumption:
Max. 3 W
Inrush current:
Max. 7A, 0.3 ms
Digital safety inputs (No. / description):
12 / „Type 2“ acc. to EN 61131-2 IN: 7 bis 10 mA at DC 24 V
Inputs for Node selection NODE_SEL0/1
(No. / description):
2 / „Type 2“ acc. to EN 61131-2 IN: 7 bis 10 mA at DC 24 V
Test output (No. / description):
8 / to check for short-circuits - overloads; max. number of inputs for each output: 2
Connection to control unit:
Proprietary 5-pole DOLD IN-RAIL-BUS
Weight:
190 g
Approvals: