Configurable Safety System SAFEMASTER PRO
102
0265525 / 16.05.19 en / 101A
E-GATE (safety gate device)
The E-GATE function block verifies the input status
of a mobile guard or safety gate device. If the mobile
guard or safety gate is open, the output is 0 (FALSE).
Otherwise the output is 1 (TRUE).
Parameters
Input Type:
- Double NC – Allows connection of components
with two NC contacts
- Double NC / NO – Allows connection of
components with one NO contact and one NC.
Manual Reset:
If selected this enables the request to reset each time
the mobile guard/safety gate is activated. Otherwise,
enabling of the output directly follows the input con-
ditions.
There are two types of reset:
Manual and Monitored. When Manual is selected the system only verifies the signal's transition from 0 to 1.
If Monitored is selected the double transition from 0 to 1 and then back to 0 is verified.
WARNING:
If the Manual Reset is active, a consecutive Input has to be used. Example: In 1 and In 2 are
used for the functional block, then In 3 has to be used for the Reset Input.
E-GATE
E-GATE