Configurable Safety System SAFEMASTER PRO
121
0265525 / 16.05.19 en / 101A
SOLID STATE DEVICE
The SOLID STATE DEVICE functional block checks
the status of the Inx inputs. If the inputs are at 24 V DC,
the Output will be 1 (TRUE), otherwise the OUTPUT
will be 0 (FALSE).
Parameters
Manual Reset:
If selected, enables the reset request after each
occupation of the area protected by the light curtain.
Otherwise, enabling of the output follows directly the
conditions of the inputs
There are two types of reset:
Manual and Monitored.
Selecting the Manual option, only transition of the signal from 0 to 1 is checked. If Monitored is selected, double
transition from 0 to 1 and return to 0 is checked.
WARNING:
If the Manual Reset is active, a consecutive Input has to be used. Example: In 1 and In 2 are
used for the functional block, then In 3 has to be used for the Reset Input.
Startup Test:
If selected, enables the power-on test of the safety device. This test requires activation and de-activation of the
device in order to run a complete functional check and enable the Output terminal. This test is required only at
machine start-up (power-on of the module).
Filter (ms):
Permits filtering of signals from the safety device. This filter can be set to between 3 and 250 ms and eliminates
any rebounds on the contacts. The duration of the filter affects calculation of module total response time.
Simultaneity (ms):
Determines that maximum permissible time (msec) between switching of two different signals from the device.
Enable Error Out:
If selected reports a fault detected by the function block.
Item Description:
This allows a description of the component's function to be entered. The text is displayed in the top part of the
symbol.