Configurable Safety System SAFEMASTER PRO
143
0265525 / 16.05.19 en / 101A
SR FLIP-FLOP
The SR FLIP FLOP operator saves the previously set status
on output Q using Set and Reset according to the following
truth table.
SET
RESET
Q
0
0
Keep memory
0
1
0
1
0
1
1
1
0
Parameters
Parameters
Enable Clear:
If selected enables the saving process to be reset.
Store output status:
If selected, it stores the output status of the Flip-flop in non-volatile memory every time it is changed. When the
system is turned on, the last stored value is restored.
It is possible to have up to 8 Flip-Flops with output status storage that will be distinguishable by an 'M'.
T FLIP-FLOP
This operator switches the Q output at each rising edge of the
T input (Toggle).
Some limitations to the use of this storage. The maximum time required for a single storage
is estimated at 50 ms and the maximum number of possible storages is set at 100000.
The total number of storages must not exceed the set limit, otherwise the operational life of
the product will be reduced, and the frequency of such storages must be sufficiently low to
enable them to be stored safely.