Configurable Safety System SAFEMASTER PRO
119
0265525 / 16.05.19 en / 101A
TESTABLE SAFETY DEVICE
The TESTABLE SAFETY DEVICE functional block
checks the status of the Inx inputs of a single or
double safety sensor, both NO and NC. Refer to the
tables below to check type of sensor and behavior.
Parameters
Input Type:
- Refer to the tables below to check type of sensor
and behaviour
Manual Reset:
If selected, enables the reset request after each acti-
vation of the device. Otherwise, enabling of the output
follows directly the conditions of the inputs.
There are two types of reset:
Manual and Monitored.
Selecting the Manual option, only transition of the signal from 0 to 1 is checked. If Monitored is selected, double
transition from 0 to 1 and return to 0 is checked.
(Single NC)
In 1
Output
0
0
1
1
(Single NO)
In 1
Output
0
0
1
1
(Double NC)
In 1
In 2
Output
Simultaneity error
0
0
0
-
0
1
0
X
1
0
0
X
1
1
1
-
(Double NC - NO)
In 1
In 2
Output
Simultaneity error
0
0
0
X
0
1
0
-
1
0
1
-
1
1
0
X
Simultaneity error = the max. time between switching of the single contacts has been exceeded.
WARNING:
If the Manual Reset is active, a consecutive Input has to be used. Example: In 1 and In 2 are
used for the functional block, then In 3 has to be used for the Reset Input.